Effects of harmonics on Electrical Equipment

VSDHarmonic distort the fundamental frequency of the mains voltage waveform which affects the performance of other electrical equipment and creates additional losses and heating.

A total harmonic voltage distortion of 2.5% can cause an additional temperature rise of 4 deg.C in induction motors. In cases where resonance can occur between the system capacitance and reactance at harmonic frequencies, voltage distortion can be even higher.

Capacitive reactance is inversely proportional to the frequency. Harmonic frequencies are multiples of the fundamental frequency which means that capacitive reactance at harmonics frequencies is inversely proportional to the harmonic order number.

This is a clear indication that capacitor banks are highly vulnerable to harmonics as capacitors present low impedance at harmonics frequency currents which could increase the dielectric losses causing overloading leading to eventual failure.

Transformers, cables and switchgear from which the converters are supplied should be de-rated to accommodate the harmonic currents and the extra losses associated with the high frequency ‘skin-effect’.

Industry standards recommends that electric supply equipments for 6-pulse converters must be de-rated by about 10% of the converter full load current and for 12-pulse converters by about 5% of the converter full load rated current.

The order of the harmonic currents that will be present can be predicted mathematically and is given by the formula:

image002

where:
n = order of the harmonics present
k = integers 1, 2, 3, …
p = pulse number of the converter

Example, for a 6-pulse converter, the harmonic order numbers will be

n = 1 x 6 - 1 = 5
n = 1 x 6 + 1 = 7
n = 2 x 6 - 1 = 11
n = 2 x 6 + 1 = 13
n = 3 x 6 - 1 = 17
n = 3 x 6 + 1 = 19
n = 4 x 6 - 1 = 23
n = 4 x 6 + 1 = 25
n = 5 x 6 - 1 = 29
n = 5 x 6 + 1 = 31

The magnitude of harmonic current is
image010

where:
In= Harmonic current at order n.
I1= Fundamental current
n= harmonic order number

5th Harmonic (250 Hz): 20.0% x I1
7th Harmonic (350 Hz): 14.3% x I1
11th Harmonic (550 Hz): 9.1% x I1
13th Harmonic (650 Hz): 7.7% x I1
17th Harmonic (850 Hz): 5.9% x I1
19th Harmonic (950 Hz): 5.3% x I1
23rd Harmonic (1150 Hz): 4.3% x I1
25th Harmonic (1250 Hz): 4.0% x I1
29th Harmonic (1450 Hz): 3.4% x I1
31th Harmonic (1550 Hz): 3.2% x I1, etc

Normally,only up to 50th harmonic is calculated as measuring instruments can only efficiently measure harmonics up to that order.

The equation for harmonic current will be
image018

From the above calculation, a 6-pulse converter theoretically will have a 4.33% more current relative to the fundamental current.

I reality however, harmonics comprises of two components, order harmonics and non-order harmonics. The order harmonics is the one we just calculated above but the non-order harmonics could not be calculated as this is directly affected by the construction of the converter.

As we know that power is directly proportional to the square of the current, 1.04332 = 1.088. This is an 8.8% increase in power consumption compare to the consumption when there are no harmonics currents. It is from this theory that the 10 % de-rating of electrical supply equipments was based on.

References:

Practical Variable Speed Drives and Power Electronics
Malcolm Barnes
Newnes, 2003

Popularity: 7%

Related Posts

Posted in Design, General.

Tagged with .


4 Responses

Stay in touch with the conversation, subscribe to the RSS feed for comments on this post.

  1. measurementequipment says

    Measurement Equipment Voltage distortion can lead this things to disaster. Electrical equipment must be seriously tested and used accordingly to its prescribe process. Dealing with the power of electricity is a very dangerous task.

  2. jess says

    hi sir. I am also an electrical engineer. can you please give me the exact site where i can download the book mentioned above for free. I just recently graduated and passed the board and i want to know more about harmonics. This is Jess again. thank you sir!

Continuing the Discussion

  1. s.pangonilo.com | Ver Pangonilo : Filipino Engineer » Effects of Harmonics on Resistive Loads linked to this post on August 20, 2009

    [...] in Harmonics category and has View commentsComments so far. As a continuation of my article on effects of harmonics on electrical equipment, let us provide an example of the effects of harmonic currents on 1-ohm resistive load drawing 1 [...]

  2. s.pangonilo.com | Ver Pangonilo : Filipino Engineer » Phase Sequence of Harmonics linked to this post on August 27, 2009

    [...] multiples of 3 and this is the current flowing into the neutral of a three phase system. From Effects of harmonics on Electrical Equipment, a 6-pulse VSD has the following harmonic [...]



Some HTML is OK

or, reply to this post via trackback.