Circuit Breaker Time-Current Characteristic Curve Made Easy

Circuit breakers time-current characteristic curve could be shaped to allow adjustment of individual circuit breakers for proper coordination between upstream and downstream protective devices.

Time-Current Characteristics

Time-Current Characteristics

The basic adjustable functions are:

Continuous Current (Ir)
Continuous Current

Continuous Current

This is the magnitude of current that a circuit breaker can carry without tripping. Ir is a percentage of the circuit breaker nominal rating (In).
Adjustment of this setting will vary the continuous current from about 20% to 100% of the circuit breaker nominal rating (In).
Example:
In = 1000A
Adjusting the setting to 60% will make the maximum continuous current rating of the circuit breaker to
= (60% x 1000) = 600 A
Long Time Delay
Long Time Delay

Long Time Delay

Long-time delay causes the breaker to wait a certain amount of time to allow temporary inrush currents, such as starting a motor, to flow without tripping.
Usually, the time adjustment is on a multiple of the continuous current rating (Ir). A common multiple is 6xIr as most motors draw current six (6) times its full load current during starting. The setting depends on the motor driven load. The unit adjustment for this setting is seconds. The long-time delay effects the position of an I2t slope which means that lower levels of contiuous current setting will allow the circuit breaker to remain online for longer periods of time.
Short Time Pickup
Short Time Pickup

Short Time Pickup

Short-time pickup is used for discrimination or selective tripping. The short-time pickup function determines the amount of current the circuit breaker will carry for a short period of time, allowing downstream protective devices to clear short-circuits without tripping the upstream device.
This setting could be adjustable from 1.5 to 10 times the trip unit continuous current setting (Ir). For example, a 1000 ampere frame can be adjusted to trip anywhere from 1500 to 10,000 amps.
If this function is set to “OFF” position, the short-time pickup and short-time delay will be disabled.
Short Time Delay
Short Time Delay

Short Time Delay

Short-time delay, used in conjunction with short-time pickup, controls the time duration before a short-time pickup trip.
There are two modes:

  • Fixed time
    A fixed instantaneous trip point, trips the breaker automatically and overrides any pre-programmed settings.
  • I2t ramp
    The I2t ramp mode is adjustable providing a short inverse time ramp. This allows better coordination with downstream thermal-magnetic circuit breakers and fuses.
Instantaneous Pickup
Instantaneous Pickup

Instantaneous Pickup

Instantaneous Pickup is used to trip the circuit breaker with no intentional delay at any current between 2 and 40 times the breaker’s continuous ampere setting (Ir).
Example:
Continuous Current Setting (Ir) = 60% x In = 600 A
Instantaneous pickup = 10 x Ir = 10 x 600 = 6000 A
A setting higher than the fixed instantaneous override will automatically trips the breaker at the fixed instantaneous override regardless of the instantaneous pickup setting.

Popularity: 32%

Most Commented Posts

Posted in Design.

Tagged with , , , , , .


9 Responses

Stay in touch with the conversation, subscribe to the RSS feed for comments on this post.

  1. A.C." TONY" TAROG, PEE says

    Congratulations! This is very informative and clear.

  2. Joe Mason says

    we always use General Electric circuit breakers at home because it is very reliable;:’

  3. firdausi says

    thanks, for information…
    it’s realy usefull for me…

Continuing the Discussion

  1. Posts about SEO as of September 17, 2009 | All About WordPress linked to this post on September 18, 2009

    [...] so many people claim. Circuit Breaker Ti&#109&#101&#45Current Characteristic Curve Made Easy – s.pangonilo.com 09/17/2&#48&#48&#57 Circuit breakers time-current characteristic [...]

  2. Why does my air compressor trip the breaker when it reaches max and cuts off, or tries to restart? | Compressor Buyer Guide linked to this post on September 20, 2009

    [...] Circuit Breaker Time-Current Characteristic Curve Made Easy – Ver … [...]

  3. Why Is Humor An Important Characteristic In A Person? | freearticlesdbonline.com linked to this post on September 21, 2009

    [...] Circuit Breaker Time-Current Characteristic Curve Made Easy [...]

  4. I would like to see or here an exact layout of how a 5 hp air compressor should be wired to a 220v breaker box | Compressor Buyer Guide linked to this post on December 30, 2009

    [...] Circuit Breaker Time-Current Characteristic Curve Made Easy – Ver … [...]

  5. Air Compressor help? | Compressor Buyer Guide linked to this post on March 27, 2010

    [...] Circuit Breaker Time-Current Characteristic Curve Made Easy – Ver … [...]

  6. What is wrong with my 650W air compressor? | Compressor Buyer Guide linked to this post on August 29, 2010

    [...] Circuit Breaker Time-Current Characteristic Curve Made Easy – Ver … [...]



Some HTML is OK

or, reply to this post via trackback.