Skip to content


Earthing Conductor Sizes

The following table lists the recommended minimum sizes of earthing conductors.
Note: This serves only as a guide, calculations are still required for verification.

Minimum Copper Earthing Conductor Size
Nominal size of active conductor mm² Nominal size of copper earthing conductor
mm²
With copper active conductors With aluminium active conductors
1 1* -
1.5 1.5* -
2.5 2.5 -
4 2.5 -
6 2.5 -
10 4 -
16 6 4
25 6 6
35 10 6
50 16 10
70 25 10
95 25 16
120 35 25
150 50 25
185 70 35
240 95 50
300 120 70
400 ≥120+ ≥95+
500 ≥120+ ≥95+
630 ≥120+ ≥120+
>630 ≥25% of active size+ ≥25% of active size+

* - May be used only when incorporated in a multicore cable
+  - A larger conductor may be required.

Source: AS/NZ 3000-2007, Table 5.1

Update (29-Jan-2011):
Calculating the fault loop impedance of a circuit will provide a more precise selection of the size of the earth conductor. See the article on fault loop impedance for more details.

Popularity: 11%


14 Responses

Stay in touch with the conversation, subscribe to the RSS feed for comments on this post.

  1. Shams-ul-Hassan says

    Can you please mention the source(Standard) behind this Table.
    If not a Standard, might be calculations.Can you please share it.
    Thanks & Regards

  2. Ver says

    Hi, Shams-ul-Hassan,

    I have added the source as requested. Thank you for visiting my blog.

  3. eric pepple says

    thanks for the blog but i am still having problem with my water heater.
    when earth conductor is connected to the heater earth terminal i feel a slight shoking sensation. when the earth conductor is disconnected i dont get the feelings. pls what does that suggest. i feel very uncomfortable putting it into use.

    pls could you assist me with possible solution to the problem.

    thanks

  4. Ver says

    You need to verify the integrity of the earth conductor. A qualified technician may be able to do it.

  5. Consolidation Calculator says

    thanks for the blog but i am still having problem with my water heater.when earth conductor is connected to the heater earth terminal i feel a slight shoking sensation. when the earth conductor is disconnected i dont get the feelings. pls what does that suggest. i feel very uncomfortable putting it into use.
    +1

  6. susil says

    can u pls help me getting those formulas for designing earthing conductors.

  7. Ver says

    There is no single formula in calculating earthing conductors. You need to know the earth fault currents, touch and step potentials and earth resistivity.

    However, if you refer to local standards in your area, there will be a recommended minimum size of earthing conductors. It will save you some calculations.

  8. Balamurali Devaraj says

    Dear Ver,
    I have an Earthing Design calculation & I would like to share the same with you to clarify my doubts. Pls provide me your maiID

  9. Ver says

    @Balamurali Dev
    Please send it to this address spa102000-contact@yahoo.com. Thanks. Ver

  10. Rizwan Agha says

    ver thanks for your so important details.I am Rizwan ,Electrical engineer.Though I am not design engineer,but some times to verify design calculations.I need to calculate the earthing conductor size for A.C equipment Air Handling Unit(30KW motor) fixed on roof, open area. It has metallic body & can be used as lightning protector.

  11. BASAVARAJ DHULEHOLI says

    Dear VER

    Can you tell the method of selection for the earhting wire for the MDP or SMP in the multy storey buildings . What we have to follow ? your table will help for this

  12. Ver says

    Hi BASAVARAJ,

    In IEC 60364-5-54:2002, Article 543 Protective conductors

    543.1 Minimum cross-sectional areas
    543.1.1 The cross-sectional area of every protective conductor shall satisfy the conditions for automatic disconnection of supply required in clause 413.1 of IEC 60364-4-41 and be capable of withstanding the prospective fault current.

    The cross-sectional area of the protective conductor shall either be calculated in accordance with 543.1.2, or selected in accordance with table 54.3. In either case, the requirements of 543.1.3 shall be taken into account.

  13. Ray says

    I have a 3MVA Transformer rated 13.80kv primary/380V secondary 3-phase. The %impedance is 8%. What would be the short-circuit current and the size of secondary earthing conductor.?

  14. Ver says

    @ray: your question is difficult to answer with that data you provided. The size of your earthing conductor depends on the standard you are using, the type of load you have and the type of installation. A cable installed on cable ladder will have different current-carrying capacity to a cable inside a conduit or a direct-buried cable.



Some HTML is OK

or, reply to this post via trackback.

*



Copyright © 2008 - 2012 Ver Pangonilo
The information on this website in may not be reproduced, republished or mirrored on another web page or website without explicit permission from Ver Pangonilo.