Skip to content


MVA Method Unbalance Fault Calculation

In the MVA Method Short Circuit Calculation tutorial, we have discussed how to calculate the three (3) phase and phase to ground fault currents.

The faults currents for three (3) phase unbalance faults are as follows:

1. Three (3) Phase Fault

3-phase-fault

2. Phase to Ground Fault

phase-to-ground-fault

3. Phase to Phase Fault

phase-to-phase-fault

4. Phase to Phase to Ground Fault

phase-to-phase-to-ground-fault

Popularity: 18%


2 Responses

Stay in touch with the conversation, subscribe to the RSS feed for comments on this post.

  1. davidcris castro says

    In the calculation of the Line to Ground Fault at the 400V bus above, the MVAsc0 = 33.33 which is the equivalent MVA of the 2MVA Transformer only. Why is it that the contributions of the 300kVA and 596kVA motors are not considered? They are not blocked by the transformer. MVAsc0 must be 41.43. May be a case of oversight?…

  2. Ver says

    The contribution of the 400V motors are already considered on the MVAsc1 = 28.28 & MVAsc2 = 28.28. Motors do not contribute to the zero sequence fault current as these are commonly delta connected or if wye connected, motors are ungrounded thus not contributing to the zero sequence current. It is only the transformer therefore which contributes to the zero sequence current.



Some HTML is OK

or, reply to this post via trackback.