Earth Fault-Loop Impedance Part 1

What is "Earth Fault-Loop Impedance"? Why is it important?

Standards define "Earth Fault-Loop Impedance" as the impedance of the earth fault-current loop (active-to-earth loop) starting and ending at the point-of-earth fault.

It is important to know the earth fault-loop impedance of a circuit to ensure that during the occurence of a phase-to-earth fault, normally an insulation fault, the magnitude of the fault current is enough to cause the operation of the protective device within the required time particularly where the touch potential exceeds 50V a.c. or 120V ripple-free d.c.

The earth fault-loop in a MEN system comprises the following parts:

  1. The active conductor as far as the point of the fault, including supply mains service line, consumers mains, submains (if any) and the final subcircuit.
  2. The protective earthing conductor (PE), including the main earthing terminal/connection or bar and MEN connection.
  3. The neutral-return path, consisting of the neutral conductor (N) between the main neutral terminal or bar and the neutral point at the transformer, including supply mains, service line and consumers mains.
  4. The path through the neutral point of the transformer and the transformer winding

The earth fault-loop impedance in its simplest form is the impedance of the active conductor olus the impedance of the earth conductor. In this case, the fault is a bolted fault, the impedance of which is zero.

The maximum disconnection time for a 230 V supply voltage shall not exceed the following:

0.4 s for final subcircuits that supply
socket-outlets having rated currents not exceed ing 63A; or
hand-held Class I equipment; or
portable equipment intended for manual movement during use.
5 s for other circuits
where it can be shown that people are not exposed to touch voltages that exceed safe values.

Please note that the maximum disconnection times will vary for other operating voltages or installation conditions, such as wet locations. etc. The fault current must be of sufficient magnitude to cause automate disconnection within the required times

In part II, we shall be discussing how to calculate fault-loop impedances.

 

Our Ads

Our Sponsors

Design Stages

Successful projects were not developed overnight. They have undergone through several stages. Missing any one stage may have caused disastrous effect on the projects causing failure.

Conceptual Design
To develop your project ideas into a more tangible perspective.
Front End Engineering and Design (FEED)
To explore possibilities to enable better control on the outcome of ideas, getting the final result without delay but more importantly without overshooting your budget.
All ideas need to be developed at this stage of the project.
Detail Design
The final stage of the design aspect of your project. Only minor, unforeseen and uncontrollable by the project team need to be implemented at this stage.
Injecting radical changes at this stage could mean redevelopment of the project concepts leading to project delays and budget overshoot.

We could offer the Electrical Engineering aspect of your project ideas. If you want to seek our help, contact us at HELP@FILIPINOENGINEER.